Skip to main content

States

While Modes represent what an asset is supposed to be doing, states show what the asset says it was actually doing.

States are crucial for accurately understanding the availability component of OEE (Overall Equipment Effectiveness). They provide essential insights into:

  • Actual running times
  • Instances and reasons for unplanned downtime
  • Categorization of downtime for analysis and improvement

States help in capturing and reporting the true operational status of assets, playing a vital role in efficiency analysis and operational optimization.

State Management

States​

There are reserved states predefined by the system such as 'Running', 'Off-line', 'Idle', 'Faulted'

StateDescription
OfflineTypically used with a state code value of 0 to indicate that the asset is powered off. It doesn't have to be 0, but modbus connections tend to return 0 in a powered off state.
RunningIndicates that the asset is operating as expected.
IdleIndicate asset is not currently running and no faults exist
FaultedIndicates a fault or error, suggesting a breakdown or malfunction

New states can be created and will generally align with the machine states or fault codes expected from the target asset.

State Types​

State Types are used to categorize the state. State types are pre-defined by the system and cannot be modified. Every state maps to one fixed state type, and the state type determines how the state affects OEE:

State TypeOEE Meaning
RunningProductive or running time
Planned DowntimeDowntime that may not count against availability
Unplanned DowntimeAvailability loss

State Categories​

State categories organize states into a hierarchy and are used solely for analysis. You can define any category via the drop down by typing in the name of a new category and selecting 'create'. Examples of categories may be 'quality', 'electrical', 'mechanical' where you would want to analyze your downtime to see how much was related to say quality issues.

Mechanical
└── Nozzle
└── Pump
Safety
Electrical

Asset Group​

This field is simply to classify certain states as say being specific to a drill press, reactor or filler. It is optional and can be left blank.


Configuring States​

Adding & Editing States​

State Management

  • State Name: Name of the state. State name must be unique
  • State Type: Select the state type, Planned Downtime, Unplanned Downtime, or Running
  • Category: Select a category for this state. Optional, can be left blank.
  • Asset Group: Specifies an asset group to which the state applies. Optional, can be left blank.
  • Enabled: Indicates if the state is active and available for use in the system.

Linking State to Assets​

States can be linked to assets. Each state is assigned a unique state code. If the state of an asset comes from a plc tag, this code should match that integer value.

  1. Select asset or assets from the asset tree.
  2. A list of states assigned to the selected assets will appear in the bottom pane showing the state link id and state code.
  3. To link a state to an asset, select one or more states and click the 'Link' button. The state will appear in the bottom pane.
  4. Assign a numeric state code for the asset state.

When an asset is OEE-enabled, Kanoa automatically links the default states Running, Faulted, Idle, and Offline.

Unlinking States from Assets​

States can be unlinked from assets using the unlink option available on the screen. If event history exists for a state, the system will not allow you to remove the link. It will instead be disabled.


State Events​